Chapter 1 — Lighting
Superseded by BNBC 2020 (in force from 11 February 2021) — see note.
Sections in this chapter
Lighting
1.1 Scope
The basic requirements for building lighting are that adequate light of the right quality is provided and that proper attention is given to the appearance and artistic features of the lighting fixtures and the effects they produce. This chapter, read together with Chapter 2 Electrical Installation covers the illumination level requirements in buildings and methods for achieving these requirements.
1.2 Terminology
This section provides an alphabetical list of the terms used in and applicable to this chapter of the Code. In case of any conflict or contradiction between a definition given in this section and that in Part 1, the meaning provided in this section shall govern for interpretation of the provisions of this chapter.
Brightness : The luminous intensity of any surface in a given direction per unit of projected area of the surface, as viewed from that direction.
COLOUR : Aspect of visual perception by which an observer may distinguish between two fields of view of the same size, shape and structure, as may be caused by differences in the spectral composition of the radiation concerned.
Colour Appearance : One of the two factors characterizing the colour qualities of a lamp. Lamps are usually divided into three groups according to their colour appearance : warm, intermediate and cool.
Colour Rendering : The colour rendering property of a lamp is described by its colour rendering index, Ra; the higher the index the better the colour rendering property. The colour rendering index of a lamp is a measure of the degree to which the psychophysical colours of objects illuminated by the lamp conform to those of the same objects illuminated by a reference lamp, under specified conditions.
Contrast : The contrast of a small object of uniform luminance seen against a background of uniform luminance is the difference between object luminance and background luminance expressed as a ratio of the background luminance.
GLARE : The sensation produced by luminance within the visual field that is sufficiently greater than the luminance to which the eyes are adapted to cause annoyance, discomfort, or loss in visual performance and visibility. The magnitude of the sensation of glare depends upon such factors as the size, position and luminance of a source, the number of sources and the luminance to which the eyes are adapted.
Glare, Direct : Glare caused by a bright light source appearing in the normal field of view of an observer.
Glare, Disability : Glare that impairs the vision, measured in terms of deterioration of visual performance (contrast sensitivity).
Glare, Discomfort : Glare that induces a feeling of discomfort; the degree of discomfort can only be measured subjectively.
Glare, Reflected : Glare caused by the reflection of bright light source on a glossy surface.
Illuminance : The quantity of light or luminous flux falling on unit area of a surface.
Illumination : The application of visible radiation to an object.
Incandescence : Emission of visible radiation by thermal excitation.
Lamp, Fluorescent : Discharge lamp in which most of the light is emitted by a layer of fluorescent material excited by the ultraviolet radiation from the discharge.
Lamp, Incandescent : Lamp in which light is produced by means of an element heated to incandescence by the passage of an electric current.
Lighting, General : Lighting designed to illuminate an area in general, without particular provision for any special local requirements within that area.
Lighting, Localized : Lighting designed to increase the illuminance at certain specified positions; for instance those at which work is carried on.
Lumen : The luminous flux emitted within unit solid angle (one steradian) by a point source having a uniform intensity of one Candela.
Luminaire : A complete lighting apparatus consisting of a lamp or lamps together with the parts designed to distribute, filter or transform the light, to fix and protect the lamps and to connect them to the supply circuit.
Luminance (at a point) : The ratio of the luminous intensity in a given direction of an infinitesimal element of the surface containing the point under consideration to the orthogonally projected area of the element on a plane perpendicular to the given direction. It is proportional to the product of the illuminance and the surface reflectance, the latter being the ratio of the reflected luminous flux to the incident luminous flux.
Luminous Flux : The quantity characteristic of radiant flux which expresses its capacity to produce visual sensation evaluated according to the values of relative luminous efficiency for the light-adapted eye.
MAINTENANCE FACTOR: The ratio of the average illuminance on the working plane, after a certain period of use of a lighting installation, to the average illuminance obtained under the same conditions for the same lighting installation when new.
Reflection FACTOR: The ratio of light reflected from a surface to the total light falling on the surface. The reflection factor varies with the roughness of the surface as well as the darkness of the colour.
Utilization FACTOR: The ratio of the flux received on the working plane to the sum of the fluxes from all the lamps in the interior.
Working Plane : A horizontal plane at a level at which work will normally be done. Where a visual task is required to be carried out throughout an interior, general illumination of the value recommended for the working plane is necessary; where the precise height and location of the task are not known or cannot be easily specified, the recommended value is that on a horizontal plane 850 mm above the floor level. For an industrial task, working plane for the purpose of general illumination levels may be taken at 760 mm above the floor level. For certain purposes, such as viewing the objects of art, the illumination levels recommended are for the vertical plane at which the art pieces are placed.
1.3 ILLUMINATION
1.3.1 Principle of Lighting
The essential features of an efficient lighting system are :
- visual comfort through adequate illumination of the working surface, prevention of glare, and avoidance of shadows,
- ease of maintenance.
The design of a lighting system shall involve :
a) careful planning of the brightness and colour pattern within both the working areas and the surroundings so that attention is drawn naturally to the important areas, detail is seen quickly and accurately, and the room is free from any sense of gloom or monotony,
b) use of directional lighting to assist perception of task detail,
c) controlling direct and reflected glare from light sources to eliminate visual discomfort,
d) minimizing flicker from certain types of lamps and paying attention to the colour rendering properties of the light,
e) the correlation of lighting throughout the building to prevent excessive differences between adjacent areas, so as to reduce the risk of accidents, and
f) the installation of emergency lighting systems, where necessary.
Table 8.1.1 shows the general impressions associated with different illuminance and colour appearances of light. Table 8.1.2 gives the various colour rendering groups with examples of use.
Table 8.1.1
General Impressions Associated with Different Illuminance and Colour Appearances
|
Illuminance |
Associated Impression | ||
|
(lux) |
(Colour Appearance) | ||
|
Warm |
Intermediate |
Cool | |
|
≤ 500 500 – 1000 1000 – 2000 2000 – 3000 ≥ 3000 |
pleasant pleasant to stimulating stimulating stimulating to unnatural unnatural |
neutral neutral to pleasant pleasant pleasant to stimulating stimulating |
cool cool to neutral neutral neutral to pleasant pleasant |
Table 8.1.2
Lamp Colour Rendering Groups
|
Colour rendering Group |
Range of Index Ra |
Colour Appearance |
Examples of Use |
|
Cool |
Textile industries, paint and printing industries | ||
|
1 |
Ra ≥ 85 |
Intermediate |
Shops, hospitals |
|
Warm |
Homes, hotels, restaurants | ||
|
2 |
70 ≤ Ra < 85 |
Intermediate |
Offices, schools, department store, fine industrial work |
|
3 |
40 ≤ Ra < 70 |
Interiors where colour rendering is of comparatively minor importance | |
|
Note : Certain applications, e.g. colour matching, may be extremely critical with regard to the colour rendering properties of the lamps used. Here, the minimum colour rendering index used shall be 90. | |||
1.3.2 Planning the Brightness Pattern
The brightness pattern seen within an interior is composed of three parts - brightness of the task itself, brightness of the immediate background of the task and brightness of the general surroundings of walls, ceiling, floor, equipment, furnishing etc.
1.3.2.1 The illumination of all work areas within a building shall be a minimum of 150 lux.
1.3.2.2 Where work takes place over the whole utilizable area of a room, the general illumination over that area shall be reasonably uniform and the diversity ratio of minimum to maximum illumination shall not be less than 0.7. This diversity ratio does not however take into account the effects of any local lighting provided for specific tasks.
1.3.2.3 When the task brightness appropriate to an occupation has been determined, the brightness of the other parts of the room shall be planned to give proper emphasis to visual comfort and interest. The recommended brightness ratios is shown in Table 8.1.3.
1.3.3 Lighting Calculations
1.3.3.1 In order to determine the necessary number of lamps and luminaires for a specified illumination level or the average illuminance obtained from a particular lighting design, the Lumen Method of calculation shall be employed.
1.3.3.2 Unless the reflection factors are known to the lighting designer, the triplet 0.7/0.5/0.3 for the reflectances of ceiling, walls and working plane respectively shall be used for offices and the triplet 0.7/0.5/0.1 for other premises. Typical reflection factors of smooth coloured surfaces are given in Table 8.1.4.
Table 8.1.3
Brightness Ratios Between Task, Adjacent Sources and Surroundings
|
For high task brightness (above 100 cd/m2) : | |
|
Maximum ratio between task brightness and the adjacent sources like table tops |
3 to 1 |
|
Maximum ratio between task brightness and illumination of the remote areas of the room not being used as work areas |
10 to 1 |
|
For low and medium task brightness (below 100 cd/m2) |
The task must be brighter than both the background and the surroundings; the lower the task brightness, the less critical is the relationship. |
Table 8.1.4
Reflection Factors of Smooth Coloured Surfaces
|
Colour |
Reflection Factor |
Colour |
Reflection Factor |
|
Flat white Ivory Buff Yellow Light tan |
0.75 – 0.850.70 – 0.750.60 – 0.700.55 – 0.650.45 – 0.55 |
Light green Grey Blue Red Dark brown |
0.40 – 0.500.30 – 0.500.25 – 0.350.15 – 0.200.10 – 0.15 |
1.3.4 Recommended Illumination Values
The recommended values of illumination required for buildings of different Occupancies, based on activity, are given in Tables 8.1.5 through 8.1.11. The initial illuminance should be higher than the recommended value to allow for the fact that the illuminance will inevitably drop below this value by the end of the cleaning and relamping period. A gradual transition of brightness from one portion to another within the field of vision is recommended so as to avoid or minimize glare discomfort.
1.3.5 Artificial Lighting to Supplement Daylight
Supplementary lighting shall be used when illumination by daylight falls below 150 lux on the working plane.
For providing supplementary artificial lighting when daylight availability becomes insufficient, cool daylight fluorescent tubes with semi-direct luminaires are recommended. To ensure a good distribution of illumination, the mounting height should be between 1.5 and 2.0 m above the work plane for a separation of 2.0 to 3.0 m between the luminaires.
1.4 LIGHT FITTINGS
An electric lamp and its fitting, globe reflector etc., shall be regarded as one unit; they shall be designed to suit each other and to give the desired distribution of light. Any focussing fittings used which enable the light distribution to be varied by adjustment of the lamp position shall also be designed for the type and size of lamp to be used.
1.4.1 Classification of Lamp Fittings
Lamp fittings shall be classified into five categories according to the proportion of the total light output in the lower hemisphere. These are: direct fittings, giving 90-100 per cent light downwards; semi-direct fittings, giving 60-90 per cent downwards; general diffusing fittings, giving 40-60 per cent light downwards; semi-indirect fittings, giving 10-40 per cent light downwards; indirect fittings, giving 0-10 per cent light downwards.
Table 8.1.5
Recommended Values of Illumination for Residential Buildings
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Dwelling houses Bedrooms General Bed-head, Dressing table Kitchens Dining rooms (tables) Bathrooms General Shaving, make-up Stairs Lounges Garages and porches Sewing and darning Reading (casual ) Home work and sustained reading Hotels Entrance halls Reception and accounts Dining rooms (tables) Lounges Bedrooms General Dressing tables, bed heads, etc. Writing rooms (tables) Corridors Stairs Laundries Kitchens Food stores Working areas Goods and passenger lifts Cloak-rooms and toilets Bathrooms Above mirror in bathrooms |
50 150 200 100 100 300 100 100 70 600 150 300 150 300 100 150 100 150 300 70 100 200 100 250 70 100 100 300 |
Table 8.1.6
Recommended Values of Illumination for Educational Buildings
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
School and College Assembly halls General When used for examinations Platforms Class and Lecture Rooms Desks Black boards Embroidery and sewing rooms Laboratories Art rooms Offices Staff rooms and common rooms Corridors Stairs Gymnasia General Matches Library Living quarters |
150 300 300 300 250 500 300 400 300 150 70 100 150 300 see Table 8.1.8 see Table 8.1.5 |
Table 8.1.7
Recommended Values of Illumination for Health Care Buildings
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Hospitals and Clinics Reception and waiting rooms Out patient department Wards General Beds Operating theatres General Tables (with adjustable operation lamp lighting) Minor Major Doctor's examination rooms Radiology departments Casualty Stairs and corridors Dispensaries |
150 150 100 150 300 2000 5000 150 100 150 100 250 |
Table 8.1.8
Recommended Values of Illumination for Assembly Buildings
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Cinemas Foyers Auditorium Corridors Stairs Libraries Shelves (stacks) Reading rooms (newspapers and magazines) Reading tables Book repair and binding Cataloguing, sorting and stock rooms Museums and Art Galleries Museums General Displays Art galleries General Paintings Restaurant Dining rooms Cash desks Self-carrying counters Kitchens Cloak-rooms and toilets Theatres Foyers Auditorium Corridors Stairs Sports Centre Halls Swimming pools Lawn or table tennis, badminton, volley ball Tournament Club Recreational Shooting ranges On target Firing point Range Football |
150 50 70 100 100 200 300 300 150 150 special lighting 100 200 100 300 300 200 100 150 70 70 100 150 150 300 200 100 300 200 50 500 |
Table 8.1.9
Recommended Values of Illumination for Business and Mercantile Buildings
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Airport Building Reception areas (desks) Baggage, customs and immigration halls Circulation areas, lounges Banks Counter, typing and accounting book areas Public areas, lobby Offices Book binding Pasting, punching and stitching Binding and folding and miscellaneous machines Finishing, blocking and inlaying Dental Surgeries Waiting rooms Surgeries General Chairs Laboratories Doctor's Surgeries Waiting rooms and consulting rooms Corridors Stairs Eyesight testing (acuity) wall charts and near vision types Jewellery and watch-making Fine processes Minute processes Gem cutting, polishing and setting Laundries and dry-cleaning works Receiving, sorting, washing, drying, ironing (calendering) and despatch Dry-cleaning and bulk machine work Fine hand ironing, pressing, inspection, mending and spotting Offices Entrance lobby and reception areas Conference rooms and executive offices General offices Business machine operation Drawing office General Boards and tracing Corridors and lift cars Stairs Lift landings Telephone exchanges Manual exchange rooms (on desk) Main distribution frame room Shops and Stores General areas Stock rooms Display windows |
300 300 150 300 150 200 200 300 300 150 300 special lighting 300 150 70 100 450 700 3000 1500 200 200 300 150 300 300 450 300 450 70 100 150 200 150 150 to 300 200 500 |
Table 8.1.10
Recommended Values of Illumination for Industrial Buildings and Processes
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Aircraft Factories and Maintenance Hangars | |
|
Stock parts productions |
450 |
|
Drilling, riveting, screw fastening, sheet aluminium layout and template work, wing sections, cowing, welding, sub-assembly, final assembly and inspection |
300 |
|
Maintenance and repair (hangars) |
300 |
|
Assembly Shops | |
|
Rough work, for example frame assembly and assembly of heavy machinery |
150 |
|
Medium work, for example machined parts, engine assembly |
300 |
|
Fine work, for example radio and telephone equipment, typewriter and office machinery assembly |
700 |
|
Very fine work, for example assembly of very small precision mechanisms and instruments |
1500 |
|
Automobile Manufacturing | |
|
Frame assembly Chassis assembly line Final assembly and inspection line Body manufacturing |
200 300 600 |
|
Parts Assembly Finishing and inspection |
200 300 700 |
|
Automobile Service Garages | |
|
Repairs Active traffic areas Storage |
250 100 25 |
|
Bakeries | |
|
General working area Decorating and icing |
150 250 |
|
Breweries and Distilleries | |
|
General working areas Brewhouse, bottling and canning plants Bottle inspection |
150 200 special lighting |
|
Carpet Factories | |
|
Winding and beaming Designing, Jacquard card cutting, setting pattern, tufting, topping, cutting, hemming and fringing Weaving, mending and inspection |
200 300 450 |
|
Chemical Works | |
|
Hand furnaces, boiling tanks, stationary driers, stationary and gravity crystallizers Mechanical furnaces, evaporators, filtration, mechanical crystallizers, bleaching Tanks for cooking, extractors, percolators |
150 200 200 |
|
Chocolate and Confectionery Factories | |
|
Mixing, blending and boiling Chocolate husking, winnowing, fat extraction, crushing and refining, feeding, bean cleaning, sorting, milling and cream making Hand decorating, inspection, wrapping and packing |
150 200 300 |
|
Clay Products and Cements | |
|
Grinding, filter presses, kiln rooms moulding, pressing, cleaning and trimming Enameling Colour and glazing - rough work Colour and glazing - fine work |
150 150 400 750 |
(Continued to next page)
Table 8.1.10 (Contd.)
Recommended Values of Illumination for Industrial Buildings and Processes
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (Ix) |
|
Clothing Factories | |
|
Matching-up Cutting, sewing |
450 |
|
Light Medium Dark |
300 450 700 |
|
Inspection | |
|
Light Medium Dark |
450 1000 1500 |
|
Hand tailoring | |
|
Light Medium Dark Pressing |
450 1000 1500 300 |
|
Dairies | |
|
General working areas Filling and bottle inspection Cooling equipment Laboratories Pasteurizers Separators |
200 450 150 450 150 150 |
|
Electrical Industries | |
|
Impregnating |
250 |
|
Winding and insulating |
500 |
|
Assembly works | |
Fine Very fine |
500 750 |
|
Testing |
500 |
|
Electricity Generating Stations (Indoor Locations) | |
|
Turbine halls Auxiliary equipment, battery rooms, blowers, auxiliary generators, switchgear and transformer chambers Boiler house (including operating floors) platforms, coal conveyors, pulverizers, feeders, precipitators, soot and slag Boiler house and turbine house Basements Conveyor house, conveyor gantries and junction towers |
150 100 70 to 100 100 70 70 to 100 |
|
Emergency lighting - all areas |
30 |
Control rooms | |
Vertical control panels Control desks Rear of control panels Switch houses |
200 to 300 300 150 150 |
|
Electricity Generating Stations (Outdoor Locations) | |
|
Switchyard Conveyors Fuel oil delivery headers Oil storage tanks Cat-walks Platforms, boiler and turbine decks Transformer and outdoor switchgear Emergency lighting - all areas |
50 50 50 50 50 50 100 30 |
|
Flour Mills | |
Rolling Sifting Packing Purifying Product control Cleaning screens, man lifts, aisleways and walkways, bin checking |
150 150 150 150 300 100 |
(Continued to next page)
Table 8.1.10 (Contd.)
Recommended Values of Illumination for Industrial Buildings and Processes
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Forge Shops and Foundries | |
|
Forge shop Annealing (furnaces) Cleaning Core making (fine) Core making (medium) Grinding and chipping Inspection (fine) Inspection (medium) Moulding (medium) Moulding (large) Pouring Sorting Cupola Shake out |
150 150 100 300 150 200 1000 300 300 150 150 200 100 150 |
|
Garages | |
Parking areas (interior) Washing and polishing, greasing, general servicing and pits |
70 150 |
|
Gas Works | |
|
Retort houses, oil gas plants, purifiers, coke screening and coke handling plants (indoor) Governor, meter, compressor, booster and exhauster houses Open type plants |
30 to 50 100 |
|
Cat-walks Platforms |
20 50 |
|
Glass Works | |
Furnace rooms, bending, annealing lehrs Mixing rooms, forming (blowing, drawing, pressing and rolling) Cutting to size, grinding, polishing and toughening Finishing (bevelling, decorating, etching and silvering) Brilliant cutting |
100 150 200 300 |
General Fine Inspection, etching and decorating |
200 500 500 |
|
Glove Making | |
|
Pressing, knitting, sorting and cutting Sewing |
300 |
|
Light Medium Dark |
300 450 700 |
|
Inspection | |
|
Light Medium Dark |
450 1000 1500 |
|
Hosiery and Knitwear | |
|
Circular and flat knitting machines, universal winders, cutting out, folding and pressing Lock-stitch and overlocking machines |
300 |
|
Light Medium Dark |
300 450 700 |
Mending Examining and hand finishing, light, medium and dark Linking or running on |
1500 700 450 |
(Continued to next page)
Table 8.1.10 (Contd.)
Recommended Values of Illumination for Industrial Buildings and Processes
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Iron and Steel Works | |
|
Manufacturing by open hearth | |
Stock yard Charging floor Slag pits Control platforms Mould yard Hot top Hot top storage Stripping yard Scrap stockyard Mixer building Calcining building |
20 100 100 100 25 100 100 100 20 100 50 |
|
Rolling mills | |
Blooming, slabbing, hot strip, hot sheet Cold strip, plate Pipe, rod, tube, wire drawing Merchant and sheared plate |
100 150 200 100 |
|
Tin plate mills | |
Tinning and galvanizing Cold strip rolling Motor room, machine room |
200 200 150 |
|
Sheet metal works | |
Miscellaneous machines, ordinary bench work Pressing, folding, stamping, shearing, punching and medium bench work |
200 200 |
|
Tin plate and galvanized sheet inspection |
500 |
|
Structural Steel Fabrication | |
Fabrication and general work Marking and cutting |
150 300 |
|
Plating shops | |
Vat, baths, buffing and polishing Final buffing and polishing |
200 500 |
|
Leather Manufacturing | |
Cleaning, tanning and stretching, vats Cutting, fleshing and stuffing Finishing and scarfing |
150 200 200 |
|
Machine shops | |
Rough bench and machine work Medium bench and machine work, ordinary automatic machines, rough grinding medium buffing and polishing Fine bench and machine work , fine automatic machines, medium grinding, fine buffing and polishing Extra fine bench and machine work, grinding fine work |
150 300 700 1000 |
|
Paint Works | |
General, automatic processes Special batch mixing Colour matching |
200 450 700 |
|
Paper Manufacturing | |
Beaters, grinding, calendering Finishing, cutting, trimming, paper making machines Hand counting, wet end of paper machine Paper machine reel, paper inspection and laboratories Rewinder Paper box manufacturing |
150 200 350 500 500 200 |
(Continued to next page)
Table 8.1.10 (Contd.)
Recommended Values of Illumination for Industrial Buildings and Processes
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Pharmaceuticals and Fine Chemical Works | |
Raw material storage Grinding, granulating, mixing and drying, tableting, sterilizing, preparation of solutions, filling, labelling, capping, wrapping and cartoning Control laboratories and testing Fine chemical processing Fine chemical finishing |
200 300 300 200 300 |
|
Printing Industries | |
|
Photo-engraving | |
Block-making, etching and staging Finishing, routing and proofing |
200 300 |
Masking and tint laying |
300 |
|
Colour Printing Inspection area |
700 |
|
Type foundries | |
Matrix making, dressing type Front assembly and sorting Hand casting Machine casting |
250 200 300 200 |
|
Printing plants | |
Machine composition and imposing stones Presses Composition room Proof reading Colour inspection and appraisal |
200 300 450 300 1000 |
|
Electrotyping Block-making, electroplating, washing and baking Moulding, finishing and routing |
200 300 |
|
Rubber Tyre and Tube Manufacturing | |
|
Stock preparation | |
Plasticating, milling Calendering |
100 150 |
|
Fabric Preparation | |
Stock cutting, bead building Tube tubing machines Tread tubing machines |
250 250 250 |
|
Tyre building | |
|
Solid tyre Pneumatic tyre |
150 250 |
|
Curing department | |
|
Tubing curing, casing curing |
350 |
|
Final Inspection | |
Tube, casing Wrapping |
1000 200 |
|
Shoe Manufacturing (Leather) | |
|
Cutting and stitching | |
|
Cutting tables Marking, buttonholing skiving, sorting and counting |
450 450 |
|
Stitching | |
|
Light materials |
300 |
|
Dark materials |
1000 |
|
Making and finishing | |
|
Nailers, sole layers, welt beaters and scarfers, trimmers, welters, lasters, edge setters, sluggers, randers, wheelers, treers, cleaning, spraying, buffing, polishing, embossing |
600 |
(Continued to next page)
Table 8.1.10 (Contd.)
Recommended Values of Illumination for Industrial Buildings and Processes
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
|
Shoe Manufacturing (Rubber) | |
Washing, coating, mill run compounding Varnishing, vulcanizing, calendering, upper and sole cutting Sole rolling, lining, making and finishing process |
100 300 500 |
|
Soap Factories | |
|
Kettle houses and ancillaries, glycerine evaporation and distillation and continuous indoor soap making | |
|
General areas Control panels |
150 200 to 300 |
|
Batch or continuous soap cooling, cutting and drying, soap milling and plodding | |
General areas Control panels and key equipment |
150 200 to 300 |
|
Soap stamping, wrapping and packing, granules making, granules storage and handling, filling and packing granules | |
|
General areas Control panels and machines Edible products processing and packing |
150 200 to 300 200 |
|
Textile Mills (Cotton) | |
Bale breaking and picking Carding and drawing Slubbing, roving, spinning, spooling Beaming and slashing on comb |
150 200 200 |
Grey goods Denims |
200 300 |
|
Weaving | |
Patterned cloth and fine counts, light Patterned cloth and fine counts, dark Plain grey cloth Cloth inspection |
300 500 200 700 |
|
Textile Mills (Silk and Synthetics) | |
|
Manufacturing Soaking, fugitive tinting, conditioning, setting or twist |
200 |
|
Winding, twisting, rewinding and coining, quilting and slashing | |
Light thread Dark thread |
200 300 |
|
Warping (silk or cotton system) on creel, on running ends, on reel, on beam, on warp at beaming |
300 |
Healding (drawing-in) Weaving Inspection |
700 300 - 500 1000 |
|
Textile Mills (Woollen and Worsted) | |
|
Scouring, carbonizing, testing, preparing, raising, brushing, pressing, back-washing, gilling, crabbing and blowing Blending, carding, combing(white), tentering, drying and cropping Spinning, roving, winding, warping, combing (coloured) and twisting Healding (drawing-in) Weaving |
150 200 450 700 |
Fine worsteds Medium worsteds and fine woollens Heavy woollens |
700 450 300 |
|
Burling and mending Perching |
700 |
|
Grey Final |
700 2000 |
|
Wood Working | |
|
Rough sawing and bench work Sizing, planing, rough sanding, medium machine and bench work glueing, veneering Fine bench and machine work, fine sanding and finishing |
150 200 300 |
Table 8.1.11
Recommended Values of Illumination for Storage Buildings
(for Occupancy classification see Chapter 2, Part 3)
|
Area or Activity |
Illuminance (lx) |
Storage Rooms of Ware House Inactive Rough bulky Medium Fine |
25 50 100 250 |
1.4.1.1 Direct fittings shall be used in situations where efficiency of illumination is the major criterion, while contract of the light source with the surroundings, shadows, and direct/reflected glare may be considered to be of relatively minor importance.
1.4.1.2 Semidirect fittings shall be used in areas where it felt that the reduction of contrast resulting from the small indirect component of light directed towards the ceiling shall be sufficient for the purpose.
1.4.1.3 General diffusing fittings shall be used where, in addition to a substantial indirect component of light aiding materially to the diffused character of the general illumination, an upward component providing a brighter background against which to view the luminance, especially for interiors with light-coloured ceiling and walls, is desirable.
1.4.1.4 Semi-indirect fittings shall be used when a comfortable brightness ratio between the ceiling and the luminaire is desirable but an efficiency of illumination, higher than that obtainable from indirect fittings is required.
1.4.1.5 Indirect fittings shall be used in situations where an environment of evenly distributed illumination is to be achieved, efficiency of illumination not being a dominant factor.
1.5 ILLUMINATION OF EXIT SIGNS AND MEANS OF ESCAPE
1.5.1 Exit Signs
1.5.1.1 All required exit signs shall be illuminated at night, or during dark periods within the area served.
1.5.1.2 Exit signs may be illuminated either by lamps external to the sign or by lamps contained within the sign. The source of illumination shall provide not less than 50 lux at the illuminated surface with a contrast of not less than 0.5. Approved self-luminous signs which provide evenly illuminated letters having a minimum luminance of 0.2 cd/m2 may also be used.
1.5.1.3 Exit signs within an area where the normal lighting may be deliberately dimmed or extinguished, such as places of entertainment, shall be illuminated either by lamps contained within the sign or by approved self-luminous signs.
1.5.2 Means of Escape Lighting
1.5.2.1 The means of escape and exit access in buildings requiring more than one exit shall be equipped with artificial lighting. The lighting facilities so installed shall provide the required level of illumination continuously during the period when the use of the building requires the exits to be available.
1.5.2.2 The intensity of illumination at floor level in the means of escape shall not be less than 10 lux, except that the minimum required floor level illumination of aisles in assembly halls, theatres and cinema during projection of motion or still pictures by directed light shall be 2 lux.
1.5.2.3 The illumination of exit signs and the lighting of the means of escape and exit access shall be powered by an alternate or emergency electrical system to ensure continued illumination for a duration of not less than 30 minutes after the failure of primary power supply.
Source: Bangladesh National Building Code 2006 (Housing and Building Research Institute). Superseded by BNBC 2020 — provided for reference. For design or official work, refer to the printed code.